If the chiller alarm sounds, red light is on and the temperature
controller display water temperature in normal or no display or display
8.88, you can judge it is water flow alarm.
CONTACT S&A
TEL:+86-20-89301885,
FAX:+86-20-84309967
SKYPE:
teyuchiller
Email:
Website: http://
Mechanical Equipment Heat Sinks Our company are focus on OEM extrusion fins Heatsinks, exporting to many abroad heat sink markets. Except aluminum alloy heatsink components making, we also are capable of other materials like bronze. Our products areas cover a large range of industries, like automobile, new energy, and medical etc. And our custom heatsink parts are of good quality and reasonable prices.
With many years' development, we have became a factory that have strong advantages at aluminum profile heatsinks, and include various Heat Sink Types that are with flexible batch of quantity making and specifications. Our extruded heatsinks are normally custom heatsink types that are of good quality and reasonable prices, they are used for mechanical equipments widely.
Mechanical Equipment Heat Sinks,Metal Cooling Plate,Aluminium Cooling Plate,Thermal Cooling Plate Suprel Metalwork Co., Ltd , https://www.suprel-cool.com
More about S&A chiller: http://
How to solve the problem for S&A chiller alarm, red light on and display 8.88
When the red light on and the controller display water temp in
normal, you can connect the water inlet with outlet by a hose, if the
alarm is eliminated, that means the internal water circulating loop work
in normal and the outside pipe blocked; If the chiller continue to
alarm, that means internal water loop blocked.
When the red light on, the temperature no display or show 8.88,
firstly we should cutt off the power line of water pump and check if the
temperature controller display water temp in normal, we can judge the
water pump failure, pls change it; Howerever if the temperature
controller can`t display water temp or show 8.88, we can judge the power
of water pump failure, and we should change another one.